16zones metal-501M
PRODUCT INTRODUCTION
This product detects the smoke by a couple of infrared diodes. The
principle of detecting
is granule in the smoke can reflect infrared light. Infrared diodes
are placed in the special
chamber. The chamber can shield external light, but don't affect
the smoke into it. While have
no smoke, the diode can receive very weak infrared light. When the
smoke entering the chamber,
diode can receive more and more lights, when the smoke attains the
certain density, the detector
can give out alarm signal. In order to reduce the interference and
lower power consumption,
the emitting circuit adopts the pulse signal.The detector is
suitable for detect the smoke in
house, shop, hotel, restaurant, office building, school, bank,
library, computer house and
storehouse etc.
PRODUCT FEATURE
ASIC ADOPTED;ANTI-LIGHT , MOTHPROOF , DUSTPROOF
SMT DESIGN, HIGH STABILITY
STRONG ADAPTABILITY FOR CIRCUMSTANCE
AUTO RESET AND TEST BY HAND
INSTALLATION AND TEST
1. Work with Microsecu wired burglar alarm control.
2. Power on, Indicating LED flashes once per 40 seconds, once per 1
second at alarm state.
3. Select proper place, fix the mounting base, then put the
detector into the base and turn it.
4. After installation, press the test button to test the output of
the detector. LED should flash
once per 1s. The detector should give out sound should send out
signal, should drive relay
5. You can press the test button to test the detector or blow a
little of smoke into the detector
to test if it work properly. The detector will recover to normal
working state when the smoke dispersed.
NOTICE
1. The detector cannot be installed under worse environment. E.g.:
coldest, hottest, dusty.
2. Please test it monthly.
3. Switch off power before clean the detector by soft brush per six
months to ensure sensitivity
and life of product.
4. For various reasons, including, but not limited to changes in
environmental conditions, electric
disruptions and tampering, the product may not perform as expected.
The user is advised to take all
necessary precautions for his/her safety and the protection of
his/her property
TECHNICAL SPECIFICATION
OPERATING VOLTAGE: 12V
STATIC CURRENT:<10uA
ALARM CURRENT: about 10~30mA
ALARM INDICATION: RED LED FLASH
SOUND LEVEL: >85dB/m
OPERATING TEMPERATURE: -10 ~+50℃
OPERATING HUMIDITY: 5~50℃ 10~90% without
DETECTING AREA: 20 square meter
SMOKE SENSITIVITY: Meet the UL standard No. 217. Factory test value
of 3.2% per foot faint dust sensor responsive.
Relay output NO/NC,COM
SIZE :107 mm dia.*35mm deep
EXECUTE CRITERION CE,ROHS,GB4715-1993 ,UL-217